Ice on the coil and ceiling
If the evaporator is buried, the defrost cycle is not clearing it: failed heater, mis-set termination probe, a timer that never advances, or a drain that has frozen solid so the meltwater has nowhere to go. The room then cools in shorter and shorter bursts until it stops holding temperature.
A defrost that terminates on time rather than on temperature is a common cause. The coil should be clear at the end of every cycle, not merely less icy than it was.
Ice around the door
Door frame heater tape, a torn gasket or a room that is not sealing will pull moist air in continuously. That moisture freezes where it enters, which is almost always the frame and the floor in front of it.
Once the door ices shut, staff prop it open to get in and out, which makes the problem worse within a day. It is worth fixing the heater before the next delivery, not after.
Ice under the floor
This one is structural. A room without floor insulation, or with a failed vapour barrier, pulls ground moisture up into the slab where it freezes. No amount of servicing fixes it, and the floor eventually heaves.
If a room was converted from chilled to frozen without a floor designed for it, the honest answer is that the floor is the fault. We will say so rather than sell another defrost repair.
In short
- — Defrost should terminate on temperature, not a timer alone.
- — Door icing is a heater, seal or pressure problem.
- — Floor ice is a construction fault, not an equipment fault.