Supply and return tell the story
A chiller's job is to deliver water at a design temperature. If the supply temperature creeps up over a season while the load has not changed, the plant is losing capacity: fouled heat exchanger, low refrigerant charge, or a control valve stuck open and sending warm water back.
The delta between supply and return shows whether the building is actually absorbing the cooling. A tiny delta with a warm building usually points at the distribution side rather than the chiller itself.
Approach temperature
Approach is the gap between the refrigerant's condensing or evaporating temperature and the water or air it is exchanging with. A widening approach means the heat exchanger surface is dirty or the charge is wrong, and it is the single most useful trend on a chiller.
It only means something if it is recorded. A one-off reading tells you almost nothing; three readings across a year tell you exactly how fast performance is degrading.
The water side is half the plant
Pumps running backwards, air in the circuit, strainers blocked and untreated water all show up as chiller problems. Before condemning a compressor, check flow, pressure differential and water quality.
That is why a maintenance visit should produce numbers, not just a signature. If your current contractor reports nothing, you have no way to know whether the plant is drifting.
In short
- — Rising supply temperature with unchanged load means lost capacity.
- — Approach temperature is the clearest trend indicator.
- — Check flow and water quality before blaming the compressor.